DF-TV7-V UV/2IR紅紫外火焰探測器是提供優(yōu)異糾錯報警功能,單元可以直接和手操終端TLU600或者由HART進(jìn)行操作配置,包括時間繼電器,靈敏度,以及輸出配置都可以由TLU600來操作,同時獲得危險區(qū)域認(rèn)證。
1,SIL2認(rèn)證,
2,UV和雙IR技術(shù)原理
3,可視范圍寬
4,繼電器,4-20MA,0-22MA,和HART輸出
特性:
- Excellent false alarm immunity
- Wide field of view
- Through lens optical check
- 4-20 mA and relay ouptuts as standard
- 4-20 mA Hart option
- SIL 2
- 總覽:
-
The Simtronics DF-TV7–V is a combined ultraviolet / infrared flamedetector offering excellent flame detection whilst maintaining outstanding false alarm immunity.
The MultiFlame DF-TV7–V is designed to respond to unwanted hydrocarbon fires, whilst maintaining a high degree of false alarm immunity. The DF-TV7-V flame detector uses combined ultraviolet/infrared (UV-2IR) optical technology that provides industry-leading immunity to false alarms based on the two IR channel design.
The device offers a wide range of output options, as standard and is suitable for use in SIL 2 applications. The detector can be configured to communicate with a wide range of fire panels, controllers, and PLCs and offer HART 7 and Syntel (Lonworks) protocols for addressable event monitoring. The devices come standard with a configurable 4-20mA or 0-22mA (PLC) output, two configurable alarm relays, and two detector status LEDs.
All MultiFlame detectors are equipped with a continuous optical lens auto-check to ensure that the optical path is clear and that the detector functions properly. Sensors can be replaced easily in the field without removing any cable glands. Devices are easy to test and configure using a TLU wireless handheld unit that is approved for use in hazardous areas. The TLU can also be used for wireless testing of the optical and output circuits. The TLU can also be used for wireless testing of the optical and output circuits.
技術(shù)參數(shù):
GENERAL Type Flame detector Product MultiFlame UV/IR Product code DF-TV7-XVA0 Manufacturer Simtronics FLAME DETECTOR Type / Principle Optical flame detection Technology Combined ultraviolet and dual infrared flame detector Fire Types Hydrocarbon fires Modularity Replaceable sensor cartridge PERFORMANCE Cone of vision 97° horizontal, 55° vertical at 50% of the axis distance Response time 1.5 sec with no temporization. Factory setting: delay 2 sec gives 3.5 sec resp. time.Adjustable delay 0 - 20 sec Detection range: - n-heptane (1 sq ft fire) 45m (130ft). - Gasoline (1 sq ft fire) 35 m (115 ft). ELECTRICAL Power supply 24V DC, range (18 - 28V DC) Power consumption 70 mA normal; 155 mA during self test Cable entry 2x M20, one entry with Exd plug - 2 additional as an option Junction box “No-touch” field cabling”, detector replaceable without opening cable glands Connection 0.3 mm2 (22 AWG) - 1.5 mm2 (16 AWG), 3 or 4 wires Analogue output signal 0-20mA, source, max. load impedance 700?. Fault signalling Diagnosis signalling in the 2.0 - 3.4mA range Relays 2 configurable relays for fire and fault Maintenance interface Wireless (IR) handheld terminal for configuration, test and diagnosis ENVIRONMENT Storage -40°C to +70°C (-40°F to 158°F) Operation -20°C to +60°C (-4°F to 140°F) Humidity 95% RH (non-condensing) Ingress IP66 RFI/EMI Complies with EN 50130-4 HOUSING EX Classification Ex d II C T6 Gb Material Epoxy coated aluminium or Stainless steel (Specify variant) Weight Aluminium: 3.3 Kg (7.3 lbs), Stainless steel: 7.4 kg (16.3 lbs) Dimensions 233L x 118D x 184H (mm), 8.78L x 4.65D x 7.25H (inches) APPROVALS ATEX Certificate DM LCIE 03 ATEX 6263 IECEx Certificate DM IECEx LCI09.0018 SIL Certificate Suitable for use in SIL2 systems MarED Certificate 23160/A0 EC + SMS.MED.D/81256/A.0 ACCESSORIES TLU600 Infrared remote control unit LT15 Test lamp (EX flame simulation torch) AS008-450 Sunshade AS030-A/X Multi-position angle wall mounting AS035-A/X Pivot ball mounting bracket AS040 Sun visor (long, open) AS041 Sun visor (long, narrow)
文檔:
Product Sheet385.55 KB
Operating Manual1.55 MB
Operating Manual LT15 (Flame Detector Test Lamp)346.03 KB
證書:
IECEx Certification170.21 KB
HART Certification47.4 KB
SIL 2 Certificate99.99 KB
應(yīng)用:
- Refineries
- Drilling and Production Platforms
- Fuel Loading Facilites
- Compressor Stations
- LNG/LPG Processing and Storage
- Gas Turbines
- Chemical Plants
- Aircraft Hangers