一、電氣絕緣檢測移動式SF6氣體回收充氣試驗設(shè)備用途
NALH型移動式SF6氣體回收充氣裝置主要用于SF6電器開關(guān)制造廠、研究所、試驗站、鐵路和鋼鐵冶煉、發(fā)電廠、送變電工程公司、超高壓輸變電站等供配電部門對GIS SF6開關(guān)電器進行抽真空、充氣、回收凈化SF6氣體及液化罐裝貯存SF6氣體。也可用于SF6開關(guān)電器產(chǎn)品在安裝、調(diào)試及檢修時使用的輔助設(shè)備,除去超標的水分、油份、塵埃等雜質(zhì),提升其絕緣性能。SF6氣體回收裝置的工作原理是用于主機將設(shè)備氣室內(nèi)的SF6氣體抽出并壓縮至臨界壓力,使其成為液體后存入貯罐中貯存。在開關(guān)室需要時,將貯罐中的氣體回充到設(shè)備室內(nèi)。其中還含有干燥系統(tǒng)、凈化系統(tǒng),保證回收的SF6氣體中的含水量、含油量及雜質(zhì)達到國家標準。同時還含有抽真空系統(tǒng),保證設(shè)備中盡量不混入空氣和雜質(zhì),也可用于別的氣體的使用。
二、裝置主要性能標
1、抽真空速率
在初壓力為0.1 Mpa終壓力小于133 pa條件下,抽真空速率為小于10m3/ h 、5m3/ h。
2、充氣速率
在初壓力小于133pa終壓力達0.8Mpa條件下,充氣速率為小于10m3/ h 、5 m3/ h。
3、回收速率
在初壓力為0.8Mpa終壓力小于100pa條件下,回收速率為2m3/h。
4、凈化SF6氣體純度(質(zhì)量控制):回收后SF6氣體的微量水份(氣體濕度)小于50PPMm/V(體積比),油份小于10PPMm/G(重量比),塵埃粒徑小于20µm。
5、凈化SF6氣體溫度控制:
制冷機溫度設(shè)定為0℃-20℃儲液罐加熱溫度設(shè)定溫度為100℃,活化分子篩加熱溫度設(shè)定為400℃。
6、 裝置的真空度保持:在133Pa壓力下保持24h,真空度上升小于400Pa。
7、凈化SF6氣體濕度控制:當氣源的六氟化硫氣體濕度為:≥1000μL/L時,經(jīng)一次回收后的氣體濕度應(yīng)低于: <80μL/L。
8、zui高儲氣壓力:<4.0Mpa。
9、裝置平均*時間≥1000h。
10、累積*運行時間≥5000h。
One, usage of equipment
NALH SF6 gas recovery inflatable device is mainly used for SF6 electrical switch manufacturers, research institutes, test stations, railway and iron and steel smelting, power plants, transmission and transformation engineering companies, high voltage power transmission and distribution substation GIS SF6 Switching electrical appliances for vacuum, gas, recovery and purification SF6 gas and liquefied cans storage SF6 gas. Can also be used for SF6 switch electrical products in the installation, commissioning and maintenance of auxiliary equipment used to remove excessive moisture, oil, dust and other impurities, to enhance its insulation properties. SF6 gas recovery device works is used for the host to the equipment within the gas chamber SF6 gas out and compressed to the critical pressure, making it into liquid storage in the storage tank. When the switching chamber is needed, the gas in the storage tank is returned to the equipment room. Which also contains drying system, purification system to ensure recovery of SF6 gas in the water content, oil content and impurities to meet national standards. But also contains a vacuum system to ensure that equipment is not mixed into the air and impurities. Can also be used for other gas use.
Two, the device main performance standard
1, the vacuum rate
In initial pressure of 0.1 Mpa final pressure of less than 133 pa conditions, the vacuum rate of less than 10m3 / h, 5m3 / h.
2, inflatable rate
In initial pressure is less than 133pa final pressure of 0.8Mpa conditions, the inflation rate of less than 10m3 / h, 5m3 / h.
3, the recovery rate
In the initial pressure of 0.8Mpa final pressure less than 100pa conditions, the recovery rate of 2m3 / h.
4, purification SF6 gas purity (quality control): recovery of SF6 gas trace moisture (gas humidity) is less than 50PPMm / V (volume ratio), oil less than 10PPMm / G (weight ratio), dust particle size is less than 20μm.
5, purification SF6 gas temperature control:
The temperature of the refrigerating machine is set to 0C to 20C. The temperature of the storage tank is set to 100C and the heating temperature of the activated molecular sieve is set to 400C.
6, the device to maintain the vacuum: 133Pa pressure to maintain 24h, the vacuum rose less than 400Pa.
7, purification SF6 gas humidity control: When the gas source of sulfur hexafluoride gas humidity: ≥ 1000μL / L, after a recovery of the gas humidity should be less than: <80μL / L.
8, the maximum storage pressure: <4.0Mpa.
9, the average time between failures ≥ 1000h device.
10, cumulative trouble-free running time ≥ 5000h.