Key Features
- High definition colour display
- Fast and easy data input
- Store 2000 appliance records
- Remote data transfer from field to office
- Bluetooth connectivity
Electrical Test Functions
- Low current earth continuity test guaranteeing accurate measurement
- Point to point testing (earth continuity and insulation resistance)*
- IEC lead test
- Protective conductor current
- Touch current
- Load power/current
- Alternative leakage current
- RCD test
- Power socket test
Earth Continuity
Test Current | +/- 200mA DC |
Display Range | 0.01 – 19.99Ω |
Pass Value | User Defined |
Insulation Resistance
Test Voltage | 500V / 250VDC @ 1mA nominal |
Display Range | 0.01MΩ - 19.99MΩ |
Pass Value | User Defined |
IEC Lead Test
Test Voltage | 5VAC nominal |
Test | Live / Neutral Checks for o/c, s/c and crossed |
Protective Conductor Current/Load
Test Voltage | Supply voltage, maximum load current 16A |
Display Ranges | 0.01mA to 19.99mA |
Pass Value | User Defined |
Touch Current
Test Voltage | Supply Voltage, maximum load current 16A |
Display Ranges | 0.00 – 3.50mA |
Pass Value | User defined |
Load Power/Current
Test Voltage | Supply Voltage, maximum load current 16A |
Test Duration | Programmable up to a maximum of 255s depending on load. i.e. max duration is reduced for high loads. |
Display Range | 0.00kVA – 4.00kVA 0.00A – 16.00A |
Alternative Leakage Current
Test Voltage | >25VAC <50VAC |
Display Range | 0.00mA to 19.99mA |
Pass Value | User Defined |
RCD Test
Test Voltage | 230V +10%, -15% |
Test Current | 30mA / 150mA rms sinusoidal |
Display Range | 0ms - 2000ms (30mA), 0ms - 40ms (150mA) |
Test method | Internal isolation to avoid tripping distribution board RCD |
Power Socket Test
Voltage Range | 207V – 253Vac |
Indicates configuration of voltage potential:- | Line potential phase to earth Line potential phase to neutral Line potential neutral to earth |
General
Memory size | 2,000 Records |
Weight | 1.5kg |
Dimensions | 230mm x 150mm x 100mm |
Power Source | Mains or rechargeable battery pack |